E-RATE CATEGORY 2

Description

McKinney Independent School District (McKinney ISD, MISD, or the District) is soliciting proposals from qualified vendors to provide E-Rate Category 2 eligible internal connections, consisting of structured cabling, network switches, wireless access points, and uninterruptible power supply (UPS)/battery backup units for eligible network equipment in support of the District’s technology infrastructure and connectivity needs. The resulting contract(s) will support the District’s participation in the Federal Communications Commission’s E-Rate Program and shall comply with all applicable E-Rate program requirements, including applicable competitive bidding, invoicing, documentation, and program compliance requirements. SCOPE & SPECIFICATIONS PURPOSE The McKinney Independent School District (“McKinney ISD, MISD, or District”) is seeking proposals from qualified proposers to furnish and install E-Rate Category 2 eligible internal connections, consisting of structured cabling, network switches, wireless access points, and uninterruptible power supply (UPS)/battery backup units for eligible network equipment, at the District locations listed below, in accordance with the specifications in this RFP and the rules of the Universal Service Schools and Libraries (E-Rate) Program. UPS/battery backup units are requested only to support E-Rate eligible Category 2 network equipment (for example, switches, routers and wireless controllers). GENERAL REQUIREMENTS All provisions of this Request for Proposal (RFP), including the Scope of Services, Technical Specifications, Contract Terms, General and Special Conditions, and required appendices, apply to all specified services and deliverables. Proposers are responsible for reviewing the entire RFP package and verifying that all requirements, specifications, and instructions are fully understood prior to submitting a proposal. Any discrepancies, ambiguities, conflicts, or omissions identified within the RFP documents shall be submitted in writing to the District's designated representative for clarification. Submit requests for clarification of discrepancies or conflicts by Friday, November 13, 2026 , 10:00 am . This allows the District time to issue an addendum if needed. All responses will be provided by written addendum and shared with all prospective proposers. If discrepancies or conflicts are found after the proposal due date, report them to the District’s representative immediately. Do not begin work or provide services until the District has formally resolved the issue. If a discrepancy or conflict between RFP sections is identified before the proposal due date but after the clarification request deadline, proposers must prepare proposals using the highest applicable performance standard, capacity, and service level for the affected component, unless otherwise directed by the District. EQUIPMENT SCOPE OF WORK McKinney ISD requests proposals for new E-Rate eligible Category 2 equipment and proposer installation services. Proposals are requested for the makes/models (or equivalent) specified in the equipment specifications and cost proposal section. Proposals containing alternative makes/models are required to submit product specifications and documentation to establish that the equipment is equivalent to the requested solution. The applicant will be the arbiter of whether the proposed solution is functionally and technically equivalent to the requested solution. The quantities requested are the applicant’s best estimate and may be adjusted based on the Proposer’s recommendations. The applicant reserves the right to increase or reduce quantities and buy some, all, or none of the listed equipment. Proposals featuring equipment that is used, open box, refurbished, or categorized in any way other than new will be disqualified. Partial proposals will be considered. The district intends on evaluating the proposals for network switches, access points, and UPS each on its own evaluation and independent of each other. Proposals for structured cabling will also be evaluated on its own evaluation. STRUCTURED CABLING SCOPE OF WORK McKinney ISD requests proposals for E-Rate Category 2 structured cabling. Proposals are requested for the makes/models (or equivalent) specified in the structured cabling specifications and cost proposal section. Proposals containing alternative makes/models are required to submit product specifications and documentation to establish that the equipment is equivalent to the requested solution. The applicant will be the arbiter of whether the proposed solution is functionally and technically equivalent to the requested solution. The quantities requested are the applicant’s best estimate and may be adjusted based on the Proposer’s recommendations. The applicant reserves the right to increase or reduce quantities and buy some, all, or none of the listed equipment. Proposals featuring equipment that is used, open box, refurbished, or categorized in any way other than new will be disqualified. The district intends on evaluating the proposals for structured cabling on its own evaluation, separate from the network switches, access points, and UPS proposals. High-level description of tasks: Install a new structured cabling system throughout the areas of the building s and portables (if any) provided in the supporting attachments Install new patch panels, fiber housings, racks, cabinets, basket tray, ladder rack, cable managers, and MDF/IDF grounding Validate, test, and label new structured cabling system Cabling and all associated equipment must be at least CAT6A compliant. Proposer will provide parts, materials, installation, and testing. Floor plans are included in the supporting attachments section. Cables are to be placed in basket tray, suspended every 4-5 feet in drop ceilings using J style hooks, or in enclosed conduit. Provide testing with documentation of cable runs to meet specifications end‐to‐end. Proposer must supply all supervision, tools, equipment, hardware, material, transportation, construction, and all other related services unless specific provisioning by McKinney ISD has been denoted. Proposer assumes total responsibility for the actions of any and all of its employees and sub-contractors if any. Proposer will be responsible for repair of all damage to the building due to the negligence of its workers and sub-contractors. Proposer must leave the job site in a clean and orderly manner every day. No leftover equipment, materials, supplies, tools, trash, etc. may be left on McKinney ISD property. All materials for disposal shall be disposed of in proper waste receptacles or taken off the property and disposed of elsewhere at proposers expense. Proposer must leave the premises clean and neat including having all ceiling tiles in place after each work session. INSTALLATION SCOPE OF WORK For this solicitation, proposer installation services are: Required Provide district requirements for installation services as outlined by the equipment and structured cabling specifications. Network switches, access points, UPS equipment, and structured cabling is needed at Minshew Elementary. This building is undergoing renovations starting May 27, 2027 and the installation of cabling and equipment will be driven by the renovation timeline. Substantial installation should be completed by July 24, 2027. UPS equipment and structured cabling is needed at Boyd High School. This building is undergoing Phase 3 renovations starting May 27, 2027 and the installation of cabling and equipment will be driven by the renovation timeline. Substantial installation should be completed by July 24, 2027. UPS equipment is needed at all other locations listed below. This work can commence on June 1, 2027 and can be completed during project business hours. Project business hours are defined as 7:00 AM to 6:00 PM, weekdays, weekends, and holidays. Substantial installation should be completed by July 24, 2027. Installation Locations: LOCATION NAME STREET ADDRESS CITY STATE ZIP CODE Minshew Elementary 300 Joplin McKinney TX 75071 Boyd High School 600 North Lake Forest Drive McKinney TX 75070 Burks Elementary School 1801 Hill St McKinney TX 75069 Caldwell Elementary School 601 W Louisiana St McKinney TX 75069 Dowell Middle School 301 S Eastridge Rd McKinney TX 75070 Eddins Student Support & Professional Learning Center (E-Rate Ineligible) 311 Peregrine McKinney TX 75070 Faubion Middle School 2000 Rollins St McKinney TX 75069 Glen Oaks Elementary School 6100 Glen Oaks Dr McKinney TX 75070 Reuben Johnson Elementary 3400 Ash Ln McKinney TX 75070 Malvern Elementary 1100 El Dorado Parkway McKinney TX 75069 McGowen Elementary School 4300 Columbus Dr McKinney TX 75070 McKinney High School 1400 Wilson Creek Pkwy McKinney TX 75069 McKinney High School North 2550 Wilmeth Road McKinney TX 75070 Press Elementary School 4101 Shawnee Dr McKinney TX 75071 Valley Creek Elementary School 2800 Valley Creek Trl McKinney TX 75070 Vega Elementary School 2511 Cattleman Drive McKinney TX 75071 Walker Elementary School 400 Cockrill Drive McKinney TX 75070 Webb Elementary School 810 E Louisiana St McKinney TX 75069 Wilmeth Elementary 901 Lacima Drive McKinney TX 75071 While the locations listed above are the sites currently planned to receive the listed equipment and services, installation may occur at any E-Rate eligible site based on the District's need at the time of purchase and delivery. DELIVERY Equipment and materials shall be delivered to the proposer's warehouse for inventory, testing, configuration, and preparation prior to installation, unless otherwise directed by the District. When delivery to the District is required, items shall be delivered to the: McKinney ISD - Central Distribution Center (CDC) 412 Interchange Street McKinney, TX 75071 QUALIFICATION OF CONTRACTORS Proposers responding to this RFP must demonstrate the qualifications, experience, and capacity required to deliver the specified services. The District will evaluate each proposer to ensure the selected provider meets all technical, operational, and compliance requirements. Minimum Qualifications To be considered, proposers must meet the following minimum qualifications: Business Experience Demonstrated experience providing the requested equipment and structured cabling services, preferably in K-12 public school environments. At least three years of experience delivering comparable services of similar scope and complexity. E-Rate Eligibility and Compliance Possession of a valid FCC Service Provider Identification Number (SPIN / 498 ID). Demonstrated knowledge of, and compliance with, FCC and USAC E-Rate Category 2 program requirements. Ability to file and support FCC Forms 473 (SPAC) and 474 (SPI). Technical Capability Ability to design, implement, and support equipment and structured cabling services that meet all RFP specifications. Capability to support a complex enterprise network. Experience supporting VoIP, video, and multicast services. Operational Capacity Sufficient personnel, equipment, and resources to deliver and support services at all District locations. Ability to complete project with stringent timelines to allow other trades to complete work prior to the start of school. Ability to provide technical support with established escalation procedures. Financial Stability Demonstrated financial stability to support long-term contract obligations. The District reserves the right to request financial statements or other documentation to verify financial capacity. Past Performance and References Proven record of satisfactory performance on similar contracts. Provide at least three references, preferably from K-12 public school districts or comparable public entities, for services performed within the past three years. Primary Proposer Responsibility If a proposal includes subcontractors or partners, the proposer must identify one primary proposer responsible for all aspects of contract performance, compliance, and service delivery. Legal and Regulatory Compliance Compliance with all applicable federal, state, and local laws, rules, and regulations. Ability to enter into a contract with the District under the terms and conditions outlined in this RFP. SUBSTITUTIONS Substitutions and Approved Equals Proposers are responsible for ensuring that all proposed equipment, services, and components meet or exceed the specifications and requirements in this RFP. All requests for substitutions or proposed “equal” equipment or services must be submitted in writing and approved by the District before the proposal due date. Substitutions will be considered only if the proposer demonstrates that the alternative is functionally and technically equivalent to, or exceeds, the specified requirements. Proposers proposing an alternate but equal brand, model, service, or solution must submit a written substitution request to the District’s designated representative at least ten (10) calendar days before the proposal due date. The request must include sufficient technical detail for the District to evaluate equivalency. If a substitution is approved, the District will issue a written addendum, which will become part of the RFP documents. If no substitutions are approved in writing before the proposal due date, only the equipment, services, and specifications identified in this RFP will be permitted. Any costs, delays, reconfiguration, or additional expenses resulting from deviations from the specified equipment, service type, or installation location are the sole responsibility of the proposer or proposers and will not result in additional cost to the District. WORKMANSHIP AND QUALITY ASSURANCE Unless otherwise specified or noted, all equipment shall be new, of the best quality, perfect and without flaws or defects. All equipment shall be delivered to the site in an undamaged condition and shall remain new and in perfect working order through the District's acceptance. All custom fabricated equipment supplied is free from defects in materials and workmanship and will be guaranteed for a period of at least (2) two years. All manufacturers’ equipment carries at least a one-year parts/labor warranty. No warranties will be applied to any existing equipment. The contractor shall turn over to the maintenance manager or authorized Distirct representative any and all warranty documentation pertaining to newly installed equipment or parts. A “no charge” statement of work shall be submitted to the District on all warranty repairs detailing the diagnosed cause and parts replaced. COMPLIANCE, CODE REGULATIONS AND STANDARDS The proposer must comply with all applicable federal, state, and local laws, codes, and regulations related to the provision, installation, operation, and maintenance of telecommunications, network, and Internet services. All work and equipment provided under this RFP must meet current industry standards and best practices. Applicable Standards and Requirements The proposer shall, at a minimum, comply with the following standards, where applicable: Federal Communications Commission (FCC) regulations applicable to telecommunications and Internet services. Universal Service Administrative Company (USAC) / FCC E-Rate Program rules and requirements for Category 2 services. National Electrical Code (NEC / NFPA 70) for any electrical work, power connections, or network equipment installations. Telecommunications Industry Association (TIA) and Electronic Industries Alliance (EIA) standards applicable to fiber-optic and Ethernet networks (including, but not limited to, TIA-568 and related standards). Institute of Electrical and Electronics Engineers (IEEE) standards applicable to Ethernet and networking technologies. Underwriters Laboratories (UL) or equivalent nationally recognized testing laboratory (NRTL) listings for all applicable electronic and network equipment. American National Standards Institute (ANSI) standards are applicable to telecommunications and network infrastructure. Building Industry Consulting Service International (BICSI) standards and best practices for telecommunications distribution systems, where applicable. State of Texas and local authority having jurisdiction (AHJ) codes and permitting requirements. Equipment and Materials All equipment must be new, commercially available, and appropriate for its intended use. Network and telecommunications equipment shall be UL-listed or NRTL-certified, where applicable. Fiber optic, network, and related components must meet or exceed manufacturer specifications and relevant industry standards. All equipment must be manufacturer-supported and not classified as end-of-life (EOL) or end-of-support (EOS) at installation. Safety and Installation Requirements Qualified and trained personnel must perform all installations in accordance with industry standards and manufacturer recommendations. Work must be coordinated to minimize disruption to District operations. The proposer is responsible for ensuring compliance with all applicable safety regulations during installation and service delivery. Responsibility for Compliance The proposer is solely responsible for ensuring that all services, equipment, materials, and installations comply with this RFP and all applicable codes and standards. All compliance-related costs must be included in the proposal and will not result in additional expense to the District. DESIGNATION OF WORK (BY OTHER TRADES UNLESS SPECIFIED BY CONTRACTOR): General Coordination Responsibilities The proposer is responsible for coordinating all subcontractors, partners, and third parties involved in delivering the proposed solution. The proposer must coordinate service delivery, installation scheduling, and testing with the District to minimize disruption to instructional and operational activities. The proposer is responsible for ensuring all services and equipment are installed at approved locations and comply with District standards and applicable codes. Facilities and Building Infrastructure (By Others Unless Noted) Unless specifically included in the proposer’s proposal: Provision of building access, pathways, wall penetrations, ceiling access, conduit pathways, sleeves, and fire-stopping shall be the responsibility of the proposer. All required building modifications or structural work must be coordinated with the District in advance. The proposer must provide timely and accurate information on location, space, power, and environmental requirements to support coordination with other trades. Electrical Work (By Others Unless Noted) Unless explicitly included in the proposer’s proposal: Provision of electrical power, outlets, circuits, grounding, and building electrical infrastructure shall be performed by others. The proposer must specify power requirements for all equipment and coordinate final connections for proposer-provided equipment. The proposer is responsible for any additional electrical work required due to deviations from specified equipment or locations. Testing and Acceptance The proposer must test all services to confirm compliance with performance, latency, and service level requirements. Services are not considered complete until accepted by the District. The proposer must correct any deficiencies identified during testing at no additional cost to the District. Responsibility for Deviations The proposer is solely responsible for any costs, delays, coordination issues, or additional work resulting from deviations from the specifications, locations, or requirements in this RFP. These shall not result in additional expense to the District. GENERAL EQUIPMENT SPECIFICATIONS All equipment furnished and installed as part of this Request for Proposal (RFP) shall be new, commercially available, and suitable for continuous operation in a K-12 public school environment. E

Published attachments
Addenda and notices
  • Addendum #1 · 1

    An addendum has been issued on the following opportunity. Any response data you have entered has been automatically copied to the addendum. Addendum Reason: This Addendum is issued to provide correct additional information and provide clarification to all prospective proposers regarding RFP2026-10-652 E-Rate Category 2. Included in this Addendum are the following: Question Response Postings – Additional wording to indicate that the response to questions submitted through OpenGov will be posted on the eProcurement Portal as well as in USAC’s E-Rate Productivity Center Removed UPS Capacity Ineligible Equipment Statement – The following statement was removed from Section 3.1 Purpose, "Any UPS capacity serving ineligible equipment must be identified and priced separately." Updated Evaluation Best Value Criteria Language - included that the District may consider the listed Texas Education Code §44.031(b) criteria when evaluating proposals to determine best value. Evaluation Criteria Pricing Update – Updated the language in Evaluation Criteria 1 to state, "PRICE FOR ELIGIBLE E-RATE PRODUCTS AND SERVICES" and reduced the points to 30, added additional pricing Evaluation Criteria 2 stating, "PRICE FOR INELIGIBLE E-RATE PRODUCTS AND SERVICES ", and assigned 5 points to the new critera. Proposers must acknowledge receipt and acceptance of the Addendum before submitting their proposal. All terms and conditions of the original RFP remain unchanged unless specifically modified by this or subsequent addenda .

  • Addendum #2 · 2

    Addendum Reason: This Addendum is issued to correct information and provide additional clarification to all prospective proposers regarding RFP2026-10-652 E-Rate Category 2. Included in this Addendum are the following: Attachment B: Questions and Answers Report – The District has received questions regarding the solicitation. The attached Questions and Answers Report contains the questions received and the District’s official responses. The attached Questions and Answers Report is hereby incorporated into and made a part of the solicitation. Respondents are responsible for reviewing the Questions and Answers Report and considering the information provided in preparing their proposals. Updated Evaluation Criterion "References" – Revised language to indicate how the District intends to evaluate References provided by Respondents. Extended Response Deadline – Extended response deadline by one (1) week. Updated Public Opening Room Location – The public opening room location has been updated. Proposers must acknowledge receipt and acceptance of the Addendum before submitting their proposal. All terms and conditions of the original RFP remain unchanged unless specifically modified by this or subsequent addenda. Please use the See What Changed link to view all the changes made by this addendum.

Public questions and answers
  • The McKinney ISD Approved Parts List includes Door Hinges, Cage Nuts/Screws and Cable Management Chases. Please provide quantities we need to include within our proposal for these items.

    The McKinney ISD Approved Parts List is a list of approved parts or equivalent. Refer to the rack elevations for each network closet in the supporting attachment of the RFP to determine the parts and accessories needed.

  • The McKinney ISD Approved parts list includes Panduit Wire Basket Tray and related items. Is it acceptable to utilize a different manufacturer such as Cablofil, WBT, Basor, etc. in lieu of Panduit?

    The specifications list all Panduit items or equivalent. This is also referenced in the MCKINNEY ISD APPROVED PARTS LIST OR EQUIVALENT section. All equivalent manufacturer part numbers will be considered. Please provide specifications detailing how the part is equivalent to the part listed.

  • Page 41 installation specifications indicates we are to run 18/2 between extension speakers and close IP ceiling speakers. Please provide drawings indicating the Extension Speakers and close IP ceiling speaker locations, or provide an estimated distance for cable & supports allocation.

    The speaker & extension speaker locations will be provided in an addendum.

  • Page 41 lists items to support Badge Readers, DPI Sensors and Lockdown buttons. Please provide drawings indicating their end device locations, or provide and estimated distance for Cable & Supports allocation.

    Badge readers, DPI Sensor, & Lockdown Button Locations will be provided in an addendum.

  • Please confirm that we need to include (1) 24-Strand fiber from the MDF to each of the identified IDF's at Minshew ES & Boyd HS Phase 3

    Yes. Please refer to 3.14. STRUCTURED CABLING SPECIFICATIONS, INSTALLATION SPECIFICATIONS, bullet C.

  • Please confirm the AT&T Dmarc Location shown on Page 11 of the supporting attachments is the only DMARC for Minshew ES for the requested Cat3 25 Pair Feeder Cable

    That is correct as per the documentation.

  • Is there desired cable jacket colors for the required 18/2, 18/4 and composite cable? Is the cable to be Plenum or Riser Rated?

    Composite cable is yellow. 18/2 & 18/4 cable is white. The cable should be plenum rated.

  • There are no mentioned requirements for sleeve pathways going into non-classroom rooms. Is it acceptable to utilize 1" minimum sized Sleeves for non-classroom rooms?

    No, we want the 2" sleeve for non-classroom rooms.

  • Please confirm if Minshew ES has existing overhead cable tray that can be used for new horizontal category/fiber cabling.

    Typically, there is existing overhead cable tray that can be used, but if there is not, it needs to be included in your proposal.

  • Please confirm if Boyd HS Phase 3 has existing overhead cable tray that can be used for new horizontal category/fiber cabling.

    Typically, there is existing overhead cable tray that can be used, but if there is not, it needs to be included in your proposal.

  • The requirement states that if no cable tray exists, the proposer will install 4"x12" Cable tray. To ensure even bids from all participating vendors, can you please provide a drawing showing the desired routing and location for the tray for both schools?

    The desired cable pathway should follow the hallways and corridors for each school.

  • The required patch cord breakdown does not account for a total of (2) Patch Cords per cable segment installed. Please confirm the patch cord requirements for both schools.

    In the patch cord section, Item A accounts for the patch cord in the MDF/IDF closet side for the switch ports. Items B-H accounts for the 2nd patch cord on the device side.

  • For the MDF to IDF Backbone fiber cabling from the MDF to each IDF at Boyd HS, Please clarify on the intent to get cabling between floors.

    The network closets at Boyd HS - Phase 3 have existing pathways between floors. The new cabling will run within these pathways.

  • Can you provide a to-scale overall drawing for each floor at Boyd HS to accurately calculate backbone fiber footages?

    Refer to the addendum section: FLOOR PLANS

  • Do we need to include demo of existing structured cabling or fiber at Minshew ES?

    No.

  • Do we need to include any demo of existing structured cabling or fiber at Boyd HS?

    No.

  • The overhead ladder rack shown in Mindshew MDF B104 appears to have two different sizes. The approved material list only indicates 12". Please provide clarity on what size ladder rack is desired.

    All ladder rack should be 12".

  • Please confirm if we need to include any surface mount raceway or surface mounted conduit to support category 6A outlets.

    Surface mounted raceway or conduit should be included for network drops that are on cinderblock or brick walls that do not already have existing raceway or conduit.

  • Please clarify when work is allowed to be done. (During normal business Hours, Overnight, Weekends, School Break, Etc.)

    Project business hours are defined as 7:00 AM to 6:00 PM, weekdays, weekends, and holidays.

  • Please provide a breakdown of the Speaker, Strobe, Clock devices indicated on the cable Matrix Drop counts for each of the 2 schools.

    The speaker, strobe, and clock devices are all IP based and need a single Cat6A drop per the requested quantity in the matrix.

  • Please clarify who is responsible for providing and installing the telecommunications bonding busbar for each IDF/MDF room.

    The grounding bus bar for each MDF/IDF room will be installed by others.

  • Do we need to include any fiber patch cords to support the new 24-strand Singlemode fiber segments running to each IDF from the MDF room?

    The District will provide the fiber patch cords.

  • Can we use 24-Fiber, 12-Duplex LC Singlemode fiber adapter panels in lieu of (2) 12-Fiber, 6-Duplex LC Singlemode fiber adapter panels for each end of the fiber backbone cables?

    Yes.

  • Is it acceptable to provide pricing for a UPS/PDU Manufacturer other than APC?

    Yes.

  • Please confirm if we need to include labor to install owner furnished wall phones at all new outlet locations

    No

  • For the horizontal cabling, would you be open to giving Belden an opportunity to compete with Panduit on this project? We can offer a high-quality, reliable solution with competitive project pricing and strong product availability to help keep the project on schedule.

    The specifications list all Panduit items or equivalent. This is also referenced in the MCKINNEY ISD APPROVED PARTS LIST OR EQUIVALENT section. All equivalent manufacturer part numbers will be considered. Please provide specifications detailing how the part is equivalent to the part listed.

  • For a company formed in 2026, may the three-year comparable-experience requirement be satisfied through the documented experience of the company's principal/owner and/or a named installation subcontractor, or must the proposing legal entity itself have three years of service history?

    The proposing legal entity must have three years of experience delivering comparable services of similar scope and complexity.

  • Must the proposer's SPIN (FCC Form 498 ID) be active at proposal submission (December 11, 2026), or will the District accept a proposer whose Form 498 has been filed with USAC and whose SPIN is pending issuance, provided it is active before award/invoicing?

    Section 2.1 in the Proposer Submissions requires respondents to provide their CC Registration Number (FRN) and E-Rate Service Provider Identification Number (SPIN / FCC Form 498 ID) at the time of submission. Proposals that omit required information may be deemed non-responsive per Section 2.3 of the Proposal Instructions.

  • If a proposer cannot supply three current school-district customers, may references be the principal's prior-project references from previous employment, or customers of a named subcontractor?

    References should be for the proposing firm. If the proposer is unable to provide three current school district customers, the proposer may provide three current customer references as permitted by the solicitation. References from previous employers of key personnel or from subcontractors do not satisfy the reference requirement for the proposing firm.

  • Is a bid bond via Surety2000 required for a partial (structured-cabling-only) proposal, and if so, at what amount or percentage? For the 100% performance/payment bonds due on award, what equivalent financial assurances has the District accepted in the past?

    For proposals including structured cabling work, a bid bond is required through Surety2000 as indicated in Section 1.6. The required bid security is 5% of the proposal amount. For performance and payment bond requirements that may be imposed upon award pursuant to Section 1.5, proposers unable to provide the required bond may submit proposed equivalent financial assurances for District review and approval in accordance with Section 1.5.1 (available once "no" is selected on 1.5. The District may consider alternatives, including a cashier's check, as an equivalent financial assurance; however, acceptance is subject to District review and approval.

  • For a newly formed company that cannot provide three fiscal years of audited financial statements, what alternative demonstration of financial capacity will the District accept (e.g., bank references, reviewed statements for the period since formation, owner financial statement)?

    Please provide audited financial statements for as many years as you have been in business. If you have been in business less than one year, please send the most current financials.

  • If a proposal names an experienced installation subcontractor under a primary proposer, will the subcontractor's experience, references, and E-Rate compliance record be evaluated toward the Section 3.7 minimum qualifications?

    No, the subcontractor's experiences, references, and E-Rate compliance record will not meet requirements for this RFP.

  • Will the District hold any additional cabling site visits before December 11 for proposers who did not attend the November 5-6 visits, or is site-visit attendance closed?

    There will be no additional site visit held.

  • The pricing form lists 200 UPS units (22 × SRTL3KRM1UNC and 178 × SRTL2K2RM1UNC) and 600 external battery packs (SRTL50RMBP1U-LI). Please confirm that the District intends three external battery packs per UPS at every location. If the count varies by site or closet, please give the quantity per UPS model or per location.

    On average, each UPS will have (3) battery packs connected. Smaller network closets with 1-2 switches have two battery packs, closets with 3-4 switches have three battery packs, closets with 5-6 switches have four battery packs, and closets with 7+ switches have 5 battery packs.

  • What runtime is the District looking for at each closet, and at roughly what load (watts or percentage of UPS capacity)?

    Based on the switch counts per closet mentioned above, the District targets one hour runtime based on the historical load.