The City of Clermont is seeking proposals from qualified respondents for the maintenance and repair of all City-owned and operated generators. These generators provide backup power for City lift stations, water well sites, Fire and Police stations, and other City buildings and facilities. Services include preventive maintenance, inspections, testing, emergency response, as-needed repairs, reporting, and coordination with City staff. Award will be made to the responsive and responsible respondent whose proposal provides the best overall value to the City. Statement of Work Project Overview The City of Clermont is seeking qualified and experienced firms to provide preventive maintenance, inspections, testing, emergency response, and as-needed repair services for City-owned and operated generators. These generators provide backup electrical power for critical City operations, including lift stations, water well sites, public safety facilities, and other City buildings. The contractor must provide all labor, supervision, materials, parts, tools, equipment, transportation, and services necessary to maintain the generators in reliable operating condition in accordance with manufacturer recommendations and the requirements of this solicitation. The contractor must coordinate all scheduled services with the City's Public Services Department and provide a maintenance schedule for City approval before beginning work. Services must include detailed inspection reports, test results, recommended corrective actions, and documentation of all work performed. The generators vary in manufacturer, model, capacity, and location. Respondents must demonstrate the qualifications, technical resources, and manufacturer service capabilities necessary to perform the required services on the equipment identified in Section 3.4. General Service Requirements The Contractor must provide preventive maintenance, inspection, testing, and repair services for the generators identified in Section 3.4. The Contractor must: Coordinate all scheduled maintenance activities with the City's designated representative and obtain approval of the proposed service schedule before beginning work. Submit an annual maintenance schedule identifying each generator, service location, required maintenance activities, and anticipated service dates. The schedule must account for all required annual maintenance, secondary inspections, and scheduled testing and replacement services. Maintain an updated schedule identifying completed services, upcoming maintenance, and outstanding work. The Contractor must provide the updated schedule to the City with each invoice. Complete all scheduled services within the applicable maintenance period unless otherwise approved by the City in writing. Any anticipated delays or changes to the approved schedule must be communicated to the City in advance and include revised completion dates for outstanding services. Coordinate required generator shutdowns or service interruptions with City personnel to minimize disruptions to City operations. Notify the City of equipment deficiencies, conditions affecting generator reliability, or other issues requiring corrective action. Provide field service reports, inspection checklists, testing results, and recommended corrective actions for all services performed. Participate in quarterly meetings with the City to review maintenance progress, completed services, outstanding repairs, and upcoming maintenance activities. Remove all debris, used materials, fluids, filters, and replaced parts and leave each service location in a clean and orderly condition. Perform all services in accordance with applicable manufacturer recommendations, safety requirements, and federal, state, and local regulations. The City reserves the right to add, remove, replace, or relocate generators during the Contract term. Services for additional or replacement generators will be performed at the applicable Contract rates. Maintenance Services Each generator included in this solicitation must receive one (1) Full Maintenance Service every twelve (12) months and one (1) additional Preventive Maintenance Inspection (PMI) approximately six (6) months after the Full Maintenance Service. Coolant flushing must be performed every thirty-six (36) months, beginning in the first year. Belts must be replaced every thirty-six (36) months, beginning in the second year. Load bank analysis must be performed every thirty-six (36) months, beginning in the third year. Maintenance services must include, at a minimum, the following: Replace engine lubricating oil during the annual Full Maintenance Service. Replace oil, fuel, and coolant filters and add corrosion inhibitors as needed. Test coolant condition during each annual Full Maintenance Service. Coolant flushing must be performed every thirty-six (36) months, beginning in the first year, or sooner if testing or inspection indicates degradation. The cooling system must be inspected during flushing for corrosion, deposits, leaks, and other deficiencies. For natural gas and LPG-fueled engines, inspect spark plugs, spark plug wires, rotors, and caps, as applicable, and replace as needed. Inspect air filters and crankcase breathers and replace as needed. Provide at least two (2) photographs documenting the condition of components recommended for replacement. Inspect belts during each PMI and replace them at least every thirty-six (36) months, beginning in the second year, regardless of apparent wear. Photographs must be provided during inspections and replacement. Inspect the generator for loose, bare, or broken wiring and connections. Document deficiencies and obtain City authorization before performing repairs outside the scheduled maintenance services. Inspect the fuel system, including fuel lines, hoses, connections, separators, and fuel pressure. Drain accumulated water from fuel separators as needed. Inspect the air intake and exhaust systems, including the exhaust manifold, valves, valve rotators, and exhaust duct, as applicable. Inspect the starting system, including batteries, battery connections, battery chargers, and starting motors. Check applicable DC voltage and current readings. Inspect fuses, electronic connections, and capacitors to ensure compliance with manufacturer specifications. Inspect and verify the operation of the automatic transfer switch during scheduled maintenance. Conduct load bank analysis for three (3) to four (4) hours in accordance with the thirty-six (36) month testing schedule, beginning in the third year, and provide a written report documenting generator performance and test results. Perform fuel testing during each annual Full Maintenance Service for all generators, using the applicable testing method based on the generator's fuel system. Testing must include appearance and haze, water content, microbial contamination, and sediment, where applicable to the fuel type. Perform oil analysis during each annual Full Maintenance Service for all generators and provide the test results to the City with the service report and invoice. Submit written service reports identifying completed maintenance activities, generator condition, deficiencies, and recommended corrective actions. All leaks must be documented in the service report. The Contractor must clean up any fluids spilled during service and properly dispose of waste materials. Any unresolved leaks or conditions affecting generator operation must be reported to the City before leaving the service location. Fuel and oil analysis results must be submitted to the City's Environmental Services Division with the applicable invoice. Invoices must include all required supporting documentation in accordance with Section 3.7, Invoicing and Payment Requirements. Preventive Maintenance Service Locations The generators covered under this solicitation are identified in the table below. The inventory includes available equipment information, generator capacities, manufacturers, models, and service locations. The Contractor must provide maintenance and repair services at the identified locations and coordinate access with the City's designated representative. Estimated quantities and generator information are provided for proposal preparation and evaluation purposes. The City does not guarantee that all listed generators will require services throughout the contract term. Generator Kw. Address Model Make Serial Number Volts LS# 3 35 1801 Rosewood Dr. DGDB-5872326 CUMM G070082069 240 LS# 4 40 1399 West Ave. DGBC-5872322 CUMM G070082071 240 LS# 5 40 1140 Linton Ct. DGHD-7082204 CUMM D080173134 240 LS#6A 250 1154 Carrol St. DQDAA*2530613 CUMM A260521863 277/480 LS# 7 40 819 W. Desoto St. DGHD-7082204 CUMM D080173132 240 LS# 9 50 614 W. Lakeshore Dr. 50DGCA CUMM J960620550 240 LS# 10 30 Seminole & Ryan St. DSKCA-595071 CUMM E090004929 240 LS# 11 30 1984 Brantley Circle DSKCA-595071 CUMM E090004927 240 LS# 13 125 301 Crystal Lake Dr. 125DSHAE-5864200 CUMM F070067822 240 LS# 14 30 512 Carrol St. DSKCA-595071 CUMM E090004928 240 LS# 15 100 295 Lake Minneola Dr. 100DGDB CUMM J960619601 240 LS# 16 40 180 W. Desoto St. DGHD-7082204 CUMM D080173135 240 LS# 17 50 142 Sunnyside Dr. DGBC-5872322 CUMM G070082070 240 LS# 18 50 575 E. Lakeshore Dr. 50.0DCA CUMM J960619886 240 LS# 23 80 590 North St. DSFAE5864199 CUMM F070067821 240 LS#31 WSFM 250 1201 W. Osceola St. LC5 CAT G5A01472 480 FIRE ADMIN 60 400 12th Street TP60-II-T2 TRADEWINDS 00016685 120 E-1 100 1151 North Ridge Blvd. 100.0DGFA CUMM J960619600 480 E-2 150 1401 North Ridge Blvd. 150.0DGFA CUMM J960619807 480 E-3 150 334 Citrus Tower Blvd. 150.0DGFA CUMM J9060619808 480 E-4 200 13410 Lake Wilma Rd. 200.0DFAA CUMM J960619833 480 E-5 200 13641 Gilbert St. 200 DFAA-84153 CUMM J960619834 480 E-6 450 13030 Hancock Rd. 450DFEC CUMM J96062087 480 E-7 150 2101 Kings Ridge Blv. 150.0GDFA CUMM J960619806 480 E-8 250 2302 Hartwood Marsh Rd. 250DFAC CUMM B980695119 480 E-8A 25 4242 Bokeelia Loop DKAF5602455 CUMM D030491269 240 E-9 250 13641 EMIL Jahna Rd. DFAC-4487919 CUMM J000159535 480 E-10 100 16834 Highway-50 100.0DGDB CUMM D980727045 480 E-11 60 13236 Whisper Bay Dr. 98A01891-5 OLY 2041110 480 E-12 40 12930 Magnolia Pointe Blvd. 98A01890-S OLY 2041109 480 E-13 25 17450 Cobblestone Court. 98A01898-5 OLY 2041115 240 E-14 275 3115 US Highway 27 DFBF3374598 CUMM F990932950 480 E-15 275 14520 John Lake Rd. DFBF3374598 CUMM F990932951 480 E-16 150 1299 Summit Greens Blvd. DGFA4476235 CUMM B000068644 480 E-17 230 1010 Jacks Lake Rd. 3306 CAT CAT 6YR03840 480 E-18 50 2835 Highland View Circle DGCA-4488156 CUMM I000153096 240 E-19 125 1457 Lake Mist Lane 125DGEA-94979 CUMM D980727054 480 E-19A 80 1221 Legendary Blvd. DGCG5707961A CUMM C050761638 480 E-20 125 1292 N. Hancock Rd. DGEA4959458 CUMM G010071607 480 E-21 100 523-L Pitt Street 100.0DGDB CUMM J960619606 480 E-21A 25 301-L Pitt Street DKAF-7088163 CUMM D080170582 240 E-21B 125 800 Skyridge Rd. DGEA4959458 CUMM E010241686 480 E-22 80 3231 White Blossom Lane DGDA5549933 CUMM A020325200 240 E-22B 35 11827 Wind Flower Ct. DGGD556519 CUMM H020398225 240 E-23 40 12066 Still Meadows Dr. DDHD5693367 CUMM J040704026 240 E-24 230 4660 Barbados Loop DFAB5695070 CUMM K040714455 480 E-25 40 10614 Lake Louisa Road DGHD5702826 CUMM A050739866 240 E-26 35 838 Grand Highway DGBB-5872326 CUMM G070082068 240 E-27 35 4587 Barrister Dr. DGGD-7082202 CUMM D080173133 240 E-28 275 2835 Majestic Isle Dr. 275DFBF CUMM I930518939 480 E-29 125 2278 Caledonian Dr. DGEA5554670 CUMM D020354469 480 E-30 230 3644 Peaceful Valley Drive DGFS5747272 CUMM A060870767 480 E-31 80 1903 Harrier Ave. DGCG5740501 CUMM I050832691 480 E-32 230 391 Balboa Blvd. DGFS57683307B CUMM F060940151 480 E-33 35 3605 Crestfield Blvd. DGBB5770158K CUMM G060951754 480 E34 250 3125 Heritage Hills Blvd. LC5 CAT GSA01608 480 E35 35 277 Giovani Blvd. DGGD-574918 CUMM B060882245 240 E36 100 11349 Lake Louisa Rd. DSGAA-7093421 CUMM E080184402 480 E37 100 626 South Ave. 100DGDB CUMM J960619896 480 E38 40 16700 Caju Rd. DSFAB7254971 CUMM J080213122 240 E39 100 2890 Hartwood Marsh Rd DSHAF-6157185 CUMM A080147281 480 E40 40 17645 Old HWY 50 DSFAB-1345437 CUMM A140627960 240 E41 60 16460 Good Hearth Blvd. DSFAD-1403534 CUMM C140658344 240 E42 200 700 Blackstill Lake Rd. D3GAE-1418468 CUMM K140764430 480 E43 25 3995 Grand Blossom Rd. C25D6 CUMM J150877923 480 E44 50 220 Camelot Loop C50D6 CUMM J160103866 240 E45 25 3403 Shallow Cove C25D6 CUMM E170188076 480 E46 50 14400 Hidden Court C50D6 CUMM E180360307 480 E47 40 22158 Valencia Blossom ST C40D6 CUMM F170200061 240 E48 500 3151 Lost Lake Rd. DFEK-1910671 CUMM B190509695 480 E49 40 3435 Buoy Circle C40D6 CUMM B190501870 480 E50 40 3151 Crestwave Dr. C40D6 CUMM E190573366 240 E51 200 4419 Renly Lane C200D6D CUMM C210894052 480 E52 40 2345 Highland Ranch Blvd. C40D6 CUMM I210981576 240 E53 40 4820 Fairwinds Ct. Winter Garden, Fl. 34787 C40D6 CUMM D220071569 240 E54 500 2611 Five Mile Rd. DFEK2290696 CUMM J230278939 277 E55 50 2668 Jumping Jack Way C50D6C CUMM L220178667 277 E56 40 5741 Meditation Dr. C40-D6 CUMM D250436144 277 E57 80 4400 Willow Wood Ave. D80-8 CAT CAT00C44VCN601533 480 E58 60 3821 Island Blvd. D60-4LC CAT CAT00C44HCN400784 240 E59 60 3096 Namaste Dr. GDO3C2441935 CUMM E250446651 480 E60 80 3710 Crooked Vine Dr. C80 D6C CUMM E240336959 460 E61 80 11021 Gallica Rose C80 D6C CUMM G250474500 277 E62 125 2902 WoodCliff Lake C125 D6C CUMM I250516316 277 E63 40 2390 Arena Blvd C40 D6 CUMM A260520800 277 PORT.5352 55 3335 Hancock Rd. 5530KB15R ONAN 0672461517 240 PORT5375 50 3335 Hancock Rd. 50ROZJ-71 CUMM 376160 240 PORT.5377 62 3335 Hancock Rd. 60REOZJB KOHLER 2039970 240 PORT.5378 62 3335 Hancock Rd. 60REOZJB KOHLER 2039969 240 PORT.3300 300 3335 Hancock Rd. DF-3300SSK KOMATSU 3691261 480 PORT. 5526 340 3335 Ha Additional Repairs If additional repairs are identified during maintenance, inspection, testing, or emergency service, the Contractor must notify the City's designated representative and provide a written estimate before performing the work. The estimate must identify the generator location, description of the deficiency, recommended repairs, required parts and materials, estimated labor hours, applicable contract rates, total estimated cost, and anticipated completion timeframe. No additional repair work may be performed without prior written authorization from the City. All authorized repairs must be performed by qualified personnel at the applicable labor rates, parts pricing, and fees established in the Contractor's Price Proposal Form. Additional charges must receive prior written approval from the City. Repair parts must be competitively priced at or below current industry list pricing. The City reserves the right to obtain alternate quotes for repair work when the proposed cost is considered excessive or unreasonable. The Contractor must complete authorized repairs promptly to minimize generator downtime and confirm proper generator operation upon completion. Safety devices, guards, and protective components must not be removed or bypassed in a manner that compromises personnel or equipment safety. Qualification Requirements The Contractor must provide qualified technicians experienced in commercial generator maintenance, repair, diagnostics, and testing. Technicians assigned to City equipment must have at least five (5) years of relevant commercial generator experience. The Contractor must: Provide applicable certifications, licenses, manufacturer training, or factory-authorized service credentials demonstrating the qualifications of assigned personnel. Identify the generator manufacturers and equipment that assigned technicians are qualified to service. Submit technician resumes or qualification summaries for City review and approval before assigning personnel to City equipment. Provide all necessary personnel, tools, diagnostic equipment, service vehicles, materials, and parts to perform the required services. Assign a designated single point of contact responsible for scheduling, reporting, emergency coordination, and communication with City personnel. Ensure that technicians wear identifiable company uniforms and appropriate personal protective equipment in accordance with applicable safety requirements. Obtain City approval before assigning replacement technicians to perform services under the contract. The Contractor must perform routine preventive maintenance, inspections, and general repairs using its own qualified employees. Subcontracting may be permitted for specialized services only with prior written approval from the City. The Contractor remains fully responsible for all work performed under the contract. The Contractor must maintain adequate staffing, equipment, and resources to provide emergency services during equipment failures, severe weather events, and declared emergencies. Emergency services must be provided in accordance with the response times and procedures proposed in the Contractor's Emergency Response Plan and accepted by the City. The accepted response-time commitments and Emergency Response Plan will become part of the resulting Contract. An updated Emergency Response Plan must be submitted annually by April 1 and whenever material changes occur. Invoicing and Payment Requirements The Contractor must submit itemized invoices for services completed and accepted by the City. Each invoice must identify the applicable Purchase Order number, generator location, generator identification, date of service, description of services performed, and applicable Contract pricing. Each invoice must separately identify the maintenance services performed, including Full Maintenance Service, secondary Preventive Maintenance Inspection (PMI), coolant flushing, belt replacement, load bank analysis, and fuel and oil analysis, as applicable. Invoices must be accompanied by completed maintenance inspection checklists, field service reports, testing results, and other documentation required under this solicitation. The Contractor must submit an updated maintenance schedule with each invoice identifying completed services, upcoming maintenance, and outstanding work in accordance with Section 3.2. The City will only approve payment for services verified as completed and accepted. Invoices for incomplete services, unauthorized repairs, or services lacking required documentation will not be approved until the deficiencies have been resolved and a proper invoice has been submitted. The Contractor must invoice at the applicable rates established in the Contract. Additional fees or charges not included in the approved Contract pricing must receive prior written authorization from the City. The City will process proper invoices for services received and accepted in accordance with the Local Government Prompt Payment Act, Sections 218.70 through 218.80, Florida Statutes, as applicable. Introduction Summary Background Contact Information Timeline The following dates are set forth for information and planning purposes; however, the City reserves the right to change the dates as needed. Respondents are advised to closely monitor any potential date changes through the Portal at https://procurement.opengov.com/portal/clermontfl . (Please note that there is no charge or fee for respondents to register and utilize the Portal). Proposal Procedures Definitions For purposes of this Request for Proposal, the following terms apply: City – The City of Clermont, Florida. Contract – The agreement resulting from this RFP, including the solicitation, addenda, accepted Proposal, and other documents incorporated into the agreement. Contractor – The Respondent awarded a Contract by the City. Portal – The City’s OpenGov electronic procurement system used for solicitation communications and Proposal submission. Proposal – The complete submission provided by a Respondent in response to this RFP. Respondent – A person,

Published attachments
Addenda and notices
Public questions and answers
  • Will the City accept a proposal where the prime Respondent provides contract management, scheduling, reporting, quality control, and City coordination, and a qualified generator service firm performs the field maintenance as a subcontractor?

    No. Section 3.6 requires the Contractor to perform routine preventive maintenance, inspections, and general repairs using its own qualified employees. Subcontracting is permitted only for specialized services with prior written City approval.

  • For the five-year business requirement (Section 4.1.C.1) and the technician experience requirement (Section 3.6), may a Respondent rely on the experience, personnel, and references of a proposed subcontractor or teaming partner?

    The prime Respondent must independently meet the five (5) year business experience requirement in Section 4.1.C.1. Technicians performing the work must meet the qualifications in Section 3.6. Proposed subcontractor qualifications and references may be submitted as supporting information but do not replace the prime Respondent's minimum qualifications.

  • which services does the City consider "specialized services" eligible for subcontracting (e.g., load bank testing, fuel/oil laboratory analysis, coolant disposal, manufacturer-specific repairs)?

    Specialized services may include load bank testing, laboratory fuel and oil analysis, coolant disposal, and manufacturer-specific repairs requiring specialized qualifications or equipment. All subcontracting requires prior written City approval, and the Contractor remains responsible for the work performed.

  • Should proposed subcontractors be identified, with their qualifications and insurance, in the proposal, or after award?

    Respondents proposing subcontractors for specialized services should identify them in their proposals and provide their proposed scope of work and relevant qualifications. Insurance documentation must meet the requirements of Section 2.9. All subcontractors are subject to City approval before performing work.

Plain text

OpenGov categories

  • 94100 · Equipment Maint, Repair, And Related Services For Power Generation And Transmission Equip.
  • 94172 · Power Generating and Transmitting Control System Maintenance and Repair Services