State and local · OpenGov
ITB 2026023 - AC Repairs and Replacements
Description
The Monroe County School District is seeking bids for the replacement of air conditioning equipment at multiple sites. Contracts will be awarded on a per site basis and contractors may bid on any or all sites listed. Contractor will include all engineering, labor, and materials to perform one for one replacement of units listed as well as the complete removal of the old systems. Repair and Replacement Cost Respondents may bid on any one or more school sites and must provide a separate lump-sum price for each site bid. Pricing must include all labor, materials, equipment, permits, removal, installation, testing, commissioning, and all other work necessary to complete the applicable Scope of Work. MCSD intends to award each site separately to the lowest responsive and responsible bidder whose bid meets the requirements of this solicitation and is in the best interest of the District. Different sites may be awarded to different Respondents. Coral Shores High School Marathon High School Sugarloaf School Key West High School Poinciana Elementary School Horace O'Bryant School Scope of Work PURPOSE The Monroe County School District (MCSD) is soliciting bids for the replacement and repair of air conditioning (AC) systems across multiple school sites. This scope of work outlines the specifications, service, and delivery requirements, and expectations from the selected contractor. Contracts will be awarded on a per-site basis; contractors may bid on any or all listed sites. Each contractor is responsible for including all necessary engineering, labor, and materials for the one-for-one replacement of specified units, including the complete removal of existing systems. Sites included in the scope of this solicitation are as follows: Coral Shores High School - 89901 Old Highway, Tavernier, FL 33070 Marathon High School - 350 Sombrero Beach Road, Marathon, FL 33050 Sugarloaf School - 255 Crane Boulevard, Upper Sugarloaf Key, FL 33042 Key West High School - 2100 Flagler Avenue, Key West, FL 33040 Poinciana Elementary School – 1407 Kennedy Dr, Key West, FL 33040 Horace O’Bryant School – 1105 Leon St, Key West, FL 33040 Mandatory Pre-Bid Site Meetings A mandatory pre-bid site meeting will be conducted at the locations and times listed below. Respondents intending to submit a bid must attend the mandatory pre-bid meeting for each school site for which they intend to submit a bid. Failure to attend and sign in at the mandatory pre-bid meeting for a site for which the Respondent submits a bid may result in the bid for that site being deemed nonresponsive. Respondents shall sign in as visitors at the front office of each school before proceeding to the meeting location. A sign-in sheet will be provided at each site to document attendance. Due to potential traffic delays between sites, the times listed below are approximate. Meetings at each site shall not begin earlier than the scheduled time. For day-of-meeting updates, Respondents may contact Jake Stacey at 305-360-1424. All questions regarding this solicitation must be submitted through the OpenGov procurement portal. Meeting Date - November 4th, 2026 Scheduled Time School Site Estimated Travel Time From Previous Site 8:00 AM Coral Shores High School Starting location 9:30 AM Marathon High School Approximately 1 hour 10:45 AM Sugarloaf School Approximately 45 minutes 11:45 AM Key West High School Approximately 20 minutes 12:50 PM Poinciana School Approximately 5 minutes 1:30 PM Horace O'Bryant School Approximately 5 minutes SPECIFICATIONS All work shall be performed in accordance with: The most current edition of the Florida Building Code The State Requirements of Educational Facilities (SREF 2014) Americans with Disabilities Act (ADA) Occupational Safety and Health Administration (OSHA) standards Start Date - Work shall commence as soon as possible on or after June 1, 2027. The contractor is responsible for coordinating with the MCSD Maintenance Department and school administration to determine the earliest date to start without interfering with normal operation. Required Completion Date - The District's target is to complete all work awarded under this solicitation by August 1, 2027. Respondents must state any proposed alternative completion dates in the project schedule included in their responses. The selected contractor shall be responsible for completing the following repair/replacement work: Coral Shores High School: CU 2807, Carrier, model# 38APD05065A12180, Serial# 1917Q59321 AHU 2807, Carrier, model# 39MN12A00176012SXS, Serial# S2102F56054 CU 2812(RA), Carrier, model# 38AUZA07A0C6A0A0C0, Serial# 1717C91585 CU 2812(OA), Carrier, model# 38APS02565A10020, Serial# 4115Q55010 AHU 2812(RA), Carrier, model# 39MN10A00175812SXS, Serial# S2102F56038 AHU 2812(OA), Carrier, model# 39MN08A00175711SXS, Serial# S2102F56034 Marathon High School: AHU 5.2.1, Carrier, model# 40RM-034—H611HC, Serial# 1607U12035 MAU 3.3, Carrier, model# 38APD03065A12020, Serial# 2216Q56732 Sugarloaf School: CU #1.1 – Carrier, model # 38AU7A12AOA6AOAOAO, serial #2114C93925 CU #1.2 – Carrier, model # 38AUZA14AOA6AOAOAO, serial #2414C94740 CU #1.4 – Carrier, model # 38AUZA16A0B6A0AOAO, serial #5113U44774 AHU #2.4 – Carrier, model # 39MN08D023WKJ22XSS, serial #2816U34283 Key West High School: CU #3-802A – Carrier, model # 38AUZA16AOC6AOAOCO, serial #1717P40432 AHU #3-802A – Unknown, model # 39THAVAC-P-LK1—AB, serial #4301F19577 CU #3-802B – Carrier, model # 38AUDC16AOC6AOAOC1, serial #1717P40364 AHU #3-802B – unknown, model # 39THAPAP-X-LUU-DB, serial #4301F19576 Poinciana Elementary School: CU #M.6 – Carrier, model # 38APD03065A12180, serial #19K17Q59311 AHU #M.6 – AAON, model # V2-D2-3-56-000:0000D000AX, serial #200602-CBCB2499 CU #M.5 – Carrier, model # 38APD03065A12180, serial #1917Q59307 AHU #M-5 – AAON, model #H2-D2-3-56-000:00B0D000AX, serial # 200602-CBCD02498 Horace O’Bryant School: CU #7 – Carrier, model # 38AUDA25A0B6AOAOAO, serial #2813U27690 AHU #7 – Trane, model # MCCA014GAT0BBC, serial #K98C23018 CU #401B – McQuay, model # RCS12F150D, serial #7920F141107178 Equipment and Work Requirements - The selected Contractor shall provide all labor, materials, equipment, and services necessary to complete the specified work, including refrigerant piping, valves, thermostatic expansion valves (TXVs), and refrigerant specialties as needed to transition from the existing equipment to the replacement systems. The following specifications shall apply. Equipment Requirements New Condensing Units (CUs) and Air Handling Units (AHUs) shall be manufactured by Addison, Carrier, York, or another manufacturer approved in writing by MCSD. Equipment Manufacturer Restriction - The use of Daikin-branded HVAC equipment is prohibited under this project. Contractors shall not furnish, install, or otherwise incorporate Daikin equipment or any equipment manufactured under the Daikin brand. Compressors shall be scroll-type unless otherwise approved by MCSD. Equipment shall have an EER greater than 10 and shall use R-454B refrigerant, subject to verification of equipment compatibility and applicable code requirements. All new equipment shall include: Factory-applied corrosion-resistant coatings, including protection for the base of the unit, meeting the District's specified corrosion-resistance requirements. Automatic reset safety features and controls, as specified. Appropriate vibration isolation and environmental protection suitable for the installation location. The use of micro-channel coils is strictly prohibited. No air conditioning equipment furnished, supplied, installed, or proposed as an equal under this Contract shall utilize micro-channel coil technology. Only equipment with conventional copper-tube and aluminum-fin coils shall be accepted. Equipment incorporating micro-channel coils shall be rejected and removed at the Contractor's expense. Existing electrical disconnects serving replacement equipment shall be inspected by the Contractor. Any disconnect that is rusted, corroded, not appropriately weather-rated, non-lockable where required, damaged, improperly sized, or otherwise unsuitable for continued service shall be replaced. Replacement disconnects shall comply with all applicable codes and shall be properly sized for the equipment being served. If equipment is relocated, a properly licensed electrical contractor shall furnish and install a new disconnect at the new equipment location, as required by applicable codes. The Contractor shall perform all work necessary to deliver a complete, fully operational HVAC system. This includes all required modifications to existing electrical systems, controls, condensate drainage, refrigerant piping, structural supports, ductwork, balancing, startup, commissioning, and any other components or services necessary for proper system performance. All equipment shall be installed in accordance with the manufacturer's installation requirements, including proper refrigerant line sizing and required accessories. The Contractor shall furnish all labor and materials necessary to provide MCSD with a complete, operational, and fully functioning HVAC system. No additional compensation shall be provided for work reasonably required to achieve a complete and functional installation, except for changes authorized in writing by MCSD under the Contract. Demolition The Contractor shall be responsible for the safe removal and pro EXPERIENCE / QUALIFICATIONS The Respondent shall hold a current and valid Certified Mechanical Contractor license issued by the appropriate Florida licensing authority and shall possess all additional licenses, certifications, registrations, and qualifications required to perform the work described in this solicitation. Respondents shall include documentation of all required licenses and certifications with their bid submissions. The documentation shall be current and valid as of the applicable submission deadline and shall remain valid throughout the performance of the Contract, as required by law. Any proposed substitution for a required license or certification shall be permitted only when legally acceptable and expressly authorized by a written amendment to this solicitation and issued by MCSD before the bid submission deadline. The Contractor shall ensure that all subcontractors performing regulated work hold the licenses and certifications required for their respective scopes of work. Failure to provide required licensing or certification documentation may result in the bid being deemed nonresponsive or the Respondent being deemed ineligible for award, subject to the solicitation requirements. REQUIRED DOCUMENTATION To be considered sufficiently responsive for award evaluation, Respondent must include in its submittal at a minimum the following documentation: Experience - documentation of successfully providing goods or services of a similar scope to those requested under this solicitation References - documentation of positive references from other work performed. All references should be documented on the Reference Form provided with this solicitation; Licenses - copies of all appropriate business licenses and professional certifications required to perform the work described in this solicitation; Insurance - proof of insurability and limits Signed Forms - signed and fully executed copies of all signable forms included in this solicitation (including notarization if applicable) Introduction NOTICE OF INVITATION TO BID NOTICE IS HEREBY GIVEN TO PROSPECTIVE PROPOSERS that on Friday, December 4, 2026 at 9:00 am , the School Board of Monroe County (the “School District” or “School Board”) will open sealed proposals for the following: ITB 2026023 ITB 2026023 - AC Repairs and Replacements Specifications and proposal documents may be accessed by going to the Monroe County School District e-Procurement Portal . The solicitation documents are also available on the district website at www.KeysSchools.com or may be requested by contacting the Internal Services Department / Purchasing Division, 241 Trumbo Road, Key West, FL 33040. Questions regarding the proposal should be directed by e-mail to Taylor Gandolfo – Buyer, at Taylor.Gandolfo@KeysSchools.com. From time to time, addenda may be issued to this solicitation. Any such addendum will be posted on Monroe County School District e-Procurement Portal . Proposals must be submitted electronically to Monroe County School District e-Procurement Portal . Hard copy or email proposals will not be accepted. All proposals must be entered in OpenGov by the date/time listed in the bid timeline within. No waivers shall be allowed for proposals which have not been submitted by the deadline date. All proposals must remain valid for a period of ninety (90) days or until the School Board approves the contract. All timely submitted proposals will be reviewed for responsiveness and suitability for the District's needs, and a recommendation will be made for the School Board to award this solicitation to the vendor whose proposal/bid represents the best interests of the Monroe County School District. The Monroe County School District reserves the right, at its sole discretion, to accept or reject any and all proposals or to waive formalities when it is in the best interest of the Board to do so. The School Board will automatically reject the response of any person or affiliate who appears on the convicted vendor list prepared by the Department of General Services, State of Florida, under Section 287.133(3) (d), F.S. (2024). Joseph Thomas Director of Internal Services Released in Key West, Florida General Information Calendar of Events Release Project Date: October 22, 2026 Newspaper Advertisement : October 29, 2026 Pre-Proposal Meeting (Mandatory): November 4, 2026, 8:00am 8:00 AM - Coral Shores High School - 89901 Old Highway, Tavernier, FL 33070 9:30 AM - Marathon High School - 350 Sombrero Beach Road, Marathon, FL 33050 10:45 AM - Sugarloaf School - 255 Crane Boulevard, Upper Sugarloaf Key, FL 33042 11:45 AM - Key West High School - 2100 Flagler Avenue, Key West, FL 33040 12:50 PM - Poinciana Elementary School – 1407 Kennedy Dr, Key West, FL 33040 1:30 PM - Horace O’Bryant School – 1105 Leon St, Key West, FL 33040 Question Submission Deadline: November 24, 2026, 5:00pm Question Response Deadline: November 25, 2026, 5:00pm Proposal Due/Bid Opening: December 4, 2026, 9:00am Monroe County School District Administration Building 241 Trumbo Road, Key West, FL 33040 Contractor Selection Date: November 20, 2026 Board Meeting: January 26, 2027 Submission Electronic Only The Monroe County School District, FL s accepting electronic submissions to ITB 2026023 - AC Repairs and Replacements . Interested bidders must create a FREE account with OpenGov Procurement by signing up at https://procurement.opengov.com/signup . Submit Electronic Responses via the School District's e-Procurement Portal: https://procurement.opengov.com/portal/keyschools-mcsd. Responses may be received up to but not later than Friday, December 4, 2026 at 9:00 am via the School District's e-Procurement Portal located at https://procurement.opengov.com/portal/keyschools-mcsd. The School District's e-Procurement Portal Clock is the official clock for the determination of all deadline dates and times. Without exception, responses will not be accepted after the submission deadline regardless of any technical difficulties such as poor internet connections. Monroe County School District, FL strongly recommends completing your response well ahead of the deadline. Once the response has been submitted and the Submission Status shows as “Submitted” the submission is complete. At that point, the Respondent will also receive an email confirmation from the School District's e-procurement Portal. Modifications and Withdrawal Respondents may withdraw their submittal electronically via the Portal at any time prior to the scheduled due date and time for submission. In order to withdraw, the respondent must navigate to their submitted proposal via the School District's e-Procurement portal and then click "Unsubmit Response" Respondents may modify their submittal electronically via the School District's e-Procurement Portal at any time prior to the scheduled due date and time for submission. In order to, withdraw, the respondent must navigate to their submitted response via the School District's e-Procurement portal and then click "Unsubmit Response". At this point, respondent's response is no longer submitted. Respondent should make the changes required and promptly re-submit response before submission date and time. Addenda & Questions Should revisions to the solicitation documents become necessary, the School District will issue an Addendum via the School District's e-Procurement. The e-Procurement Portal will send an automated email notification to all Respondents on the Followers list. Addenda information will be available to view and acknowledge via the School District's e-Procurement. It is the sole responsibility of the Respondent to ensure that they obtain information related to any Addenda, and acknowledge any and all Addenda electronically in the Portal as part of their Response. Failure to do so will result in rejection of the Response and a determination as “Non-Responsive.” Respondents shall submit all inquiries regarding this bid via the School District’s e-Procurement Portal until Tuesday, November 24, 2026 on 5:00 pm . All answers to inquiries will be posted on the School District’s e-Procurement Portal. Respondents may also click “Follow” on this solicitation to receive an email notification when answers are posted. It is the responsibility of the respondent to check the website for answers to inquiries. Conditions and Limitations a) The School Board reserves the right to reject any and all proposals, to waive any irregularities or informality, and to accept or reject any items or combination of items. b) The School Board may consider all proposals and reserves the right to award the contract(s) in the best interest of the School Board. c) A proposal may not be withdrawn before the expiration of ninety (90) days after the proposal due date. d) The School Board will not reimburse proposers for any costs associated with the preparation and submittal of any proposal, or for any travel and per diem costs incurred. e) Proposer acknowledges that all information contained within their proposal is part of the public domain as defined by the State of Florida Public Records Law. f) Proposers, their agents and/or associates shall refrain from contacting or soliciting any official of the Monroe County School District or School Board member regarding this proposal during the selection process. Failure to comply with this provision may result in disqualification of the proposer. g) The proposal and the related responses of the selected proposer will by reference become part of the formal agreement between the selected proposer and the School Board. h) The School Board and the selected proposer(s) will negotiate a contract or contracts as to terms and conditions. In the event an agreement cannot be reached with the selected proposer in a timely manner, the School Board reserves the right to select an alternative proposer. i) Cancellation: In the event the proposer violates any of the provisions of this proposal, the Superintendent shall give written notice to the proposer stating the deficiencies and unless deficiencies are corrected within five (5) days, recommendations will be made to the School Board for immediate cancellation. The School Board reserves the right to terminate any contract resulting from this proposal at any time for any reasons, upon giving thirty (30) days prior written notic
Published attachments
Addenda and notices
Official Notice #1: ITB 2026023 Pre-Bid Sign-In · 1
Addendum #1 · 1
Please use the See What Changed link to view all the changes made by this addendum.
Addendum #2 · 2
Please use the See What Changed link to view all the changes made by this addendum.
Official Notice #2: Notice of Revised Bid Schedule · 2
Please be advised that, due to a correction to the bid information, the bid schedule has been revised as follows: Q&A Period Reopened: November 17, 2026 Deadline to Submit Questions: November 24, 2026 at 5:00 PM Deadline for District Responses: November 25, 2026 at 5:00 PM Bid Submission Deadline / Opening: December 4, 2026, at 9:00 AM The Q&A period has been reopened to allow vendors additional time to review the corrected bid information and submit any questions. Please ensure all questions and bid submissions are received by the applicable deadlines. All other solicitation requirements remain unchanged. We apologize for any inconvenience and appreciate your understanding.
Addendum #3 · 3
Please use the See What Changed link to view all the changes made by this addendum.
Public questions and answers
Pre Proposal meeting still happening even with weather and flooding conditions?
Yes the pre-bid meeting is still scheduled to take place as planned.
please confirm if secondary drain pans are required for AHU's located on second floor.
The solicitation does not specifically require secondary drain pans for AHUs located on the second floor. However, all installations shall comply with all applicable codes, permitting requirements, manufacturer installation instructions, and the scope requirement to provide a complete and fully operational HVAC system. Secondary drain pans shall be provided where required to meet those requirements.
Please confirm stainless cable tie downs are required on ALL condenser replacements.
Yes. Stainless steel cable tie-downs shall be provided on all condenser replacements. All outdoor condensing units shall be installed with code-compliant anchoring and tie-down systems designed to meet applicable wind-load requirements and manufacturer installation recommendations. Contractors shall include all materials, labor, and accessories necessary for a complete installation.
Please confirm that solenoid valves, dryer shells and sight glasses must be replaced.
Yes. Solenoid valves, filter dryer shells and cores, and sight glasses shall be replaced as part of each HVAC system replacement. The intent of the project is to provide a complete, fully operational refrigeration system incorporating new components throughout the refrigerant circuit.
ITB lists only MAU 3.3 carrier condenser model and serial#. please confirm that the Aaon AHU for MAU 3.3 is being replaced also,
The ITB correctly identifies the equipment included for replacement at Marathon High School as MAU 3.3, Carrier, model 38APD03065A12020, Serial No. 2216Q56732. The associated AAON air handling unit is not included in the scope of work and is not being replaced under this solicitation. Bidders shall include only the equipment specifically listed in the ITB as part of their base bid.
Please confirm that the following equipment observed during the mandatory walkthrough is intentionally excluded from the base replacement scope: Coral Shores High School: Carrier model 38APS02565A10020 Sugarloaf School: Carrier R-32 model 38RCD02563A3G184 Sugarloaf School: Carrier R-32 CU-15, model 38RCD06063A4G104 Horace O'Bryant School: McQuay AHU01 (EVENT), Section 2 of 3, Serial FB0U110401206 These units were observed and photographed during the site walkthrough but are not listed among the replacement equipment in Section 4.2(D). Please confirm that bidders should not include replacement of these units in the base bid.
Yes, the equipment you listed is not included in the ITB scope of work and shall NOT be included in any proposal. Bidders shall base their proposals on the equipment specifically identified in Section 4.2(D) of 2027 AC replacement scope of work. Equipment not listed in the replacement schedule is not included in the base scope of work and shall not be included in the base bid amount.
this unit is a (2) condenser system ITB only lists (1) condenser. the replacement of this AHU requires replacement of both condensers.
The referenced AHU is served by a two-condenser system. Although the ITB currently lists only one condenser, replacement of the AHU requires replacement of both associated condensers to provide a complete and fully operational HVAC system. Both condensers (CU 2812 and CU 21812(2)) have been added to the scope of work and shall be included in the Contractor's base bid.
If the existing refrigerant lines are not adequate for the new refrigerant, should they be replaced for the correct size of the new refrigerant.
Yes, IAW ITB scope of work, "The Contractor shall perform all work necessary to deliver a complete, fully operational HVAC system." and "All equipment shall be installed in accordance with the manufacturer's installation requirements, including proper refrigerant line sizing and required accessories."
Just to make sure, the use of Micro- Channel or similar style is strictly prohibited, as per the ITB (4.2 “Specifications”; Letter E “Equipment and Work Requirements”; Number 1 “Equipment Requirements”; Letter e). You will only accept Aluminum Fin, Copper Tube Condenser Coils.
That is correct. IAW ITB scope of work "The use of micro-channel coils is strictly prohibited. No air conditioning equipment furnished, supplied, installed, or proposed as an equal under this Contract shall utilize micro-channel coil technology. Only equipment with conventional copper-tube and aluminum-fin coils shall be accepted. Equipment incorporating micro-channel coils shall be rejected and removed at the Contractor's expense."